Specifications
Specifications of the Indicator (EW501)
Name Gas Leak Detector (MODEL:EW501)
Detector Gases LPG LNG City Gas(Methane, Butane, Propane) Combustible Gas
Power AC 220V. 60㎐ (AC 230V 50㎐ AC110V/ 50㎐ option)
Consuming Electricity 1 UNIT 당 5W
Operating Temperature Range and Humidity -10℃~ 50℃, 0~95% RH
Readout Range 0 ~ 100% LEL
Alarm Point Within 25% (user adjustable*Variable setting)
Response Time Within 20 seconds
Gas Alarm Signal Visual Alarm(unit) (red)
Visual Alarm(main) (yellow)
Audion Alarm(main) inter mitten piezo-90dB at 1m
Operating Indicator Lighting of LED LAMP (green)
Trouble Indicator Lighting of LED LAMP (Red)
Warm up Time at Early Stage 60 seconds
Connection Cable VCT or CVVS above 0.75mm SQ Use over
Preliminary Power Ni-cd 700mAh DC 12v, Battery charger built in
Outer Output DC 9V(15mA output).NON contact point NO.NC.COM(relay contact point)
Contact Point AC 110V/220V 1A. DC 12~24 2A
Specifications of the Detector
Type Expansion Type
Detector Gases LPG LNG City Gas(Methane, Butane, Propane) Combustible Gas
Sensor Type Catalytic, Combustion (Hot-wire type) Diffusion Type
Operating Temperature Range and Humidity -20℃~ 40℃, 0~95% RH
Explosion-proof Type ExdⅡBT
Cable Connector Inside Dia 16mm/ Outer Dia 23mm
Dimension 137*142*75
Weight 1,036g
Readout Range 0~100%(LEL)
Response Time Within 20 seconds
Outer Material Quality Aluminum
Operation Place Inside the Buillding